GENEQ > Environment > Air Capture Hood

AccuBalance Capture Hood
model  8375


Features and Benefits
• Ergonomic design and ultra light weight for easy one person operation
• Detachable digital manometer for use in other applications with Pitot, air flow, temperature, velocity matrix, or relative humidity probes
• Back pressure compensated
• Multiple hood sizes available
• Bio-Safety hood kit available

The TSI 8375 Capture Hood is a multipurpose electronic air balancing instrument for reading air volume flow at diffusers, and grilles. It is ideally suited for commissioning agents, facilities managers, health and safety specialists, test engineers, and test and balance professionals. This ultra light weight, ergonomically designed kit saves time and money while helping to create a healthy and energy efficient environment.

Optional Accessories
• Pitot tubes
• 16-point velocity matrix with telescoping handle
• Air flow probe
• Temperature probe
• Temperature/humidity probe
• Multiple hood sizes available
• Bio-safety cabinet hood kit

Specifications
ACCUBALANCE Model 8375
Volume
Range 25 to 2,500 ft3/min (42 to 4250 m3/h) capture hood
Accuracy ±3% of reading ±7 ft3/min (±12 m3/h) at flows
>50 ft3/min (>85 m3/h)
Units ft3/min, m3/h, m3/min, l/s
Resolution 1 ft3/min (1 m3/h)
Velocity
Range (Pitot Probes) 25 to 8,000 ft/min (0.125 to 40 m/s)
Range (Airflow Probe) 25 to 5,000 ft/min (0.125 to 25 m/s)
Velocity Matrix 25 to 2,500 ft/min (0.125 to 12.5 m/s)
Accuracy ±3% of reading ±7 ft/min (±0.04 m/s) at
velocities >50 ft/min (0.25 m/s)
Units ft/min, m/s
Resolution 1 ft/min (0.01 m/s)
Pressure 
Differential Pressure ±15 in. H2O (±3735 Pa ); 150 in. H2O
(37.5 kPa) maximum safe operating pressure
Absolute Pressure 15 to 40 in. Hg (356 to 1016 mm Hg)
Accuracy ±2% of reading ±0.001 in. H2O (±0.25 Pa )
static and differential; ±2% of reading
absolute
Units in. H2O in. Hg, Pa, hPa, kPa, mm Hg, cm Hg,
mm H2O, cm H2O
Resolution 0.00001 in. H2O (0.001 Pa) static and
differential; 0.01 in. Hg (1 mm Hg) absolute
RH
Range 0 to 95% RH temperature/RH probe
Accuracy ±3% RH
Resolution 0.1% RH
Temperature
Sensor in Base 40 to 140°F (4.4 to 60°C)
Temperature Probe -40 to 250°F (-40 to 121°C)
Temperature/RH Probe 14 to 140°F (-10 to 60°C)
Accuracy ±0.5 °F (±0.3°C) from 32 to 160°F
(0 to 71°C); Units °F, °C
Resolution 0.1°F (0.1°C)