GENEQ > Environment > Panel & Process Meters

Digital Panel Meter
Model PD765

The Trident handles all the common process display, alarm, and on-off control applications with simplicity, reliability, accuracy, and ease. One model accepts process (4-20 mA, 1-5 V, etc) and temperature (RTD and T/C) inputs.

You make the choice – any time. Setup and programming is quick, intuitive and can be done from the front panel or with a PC. And once you’ve programmed one meter, you can use the Trident’s Copy function to clone more!

FEATURES
  • Process, TC& RTD Inputs
  • NEMA 4x Front
  • Universal Power Supply
  • Serial Communication
  • Shallow Depth Case
  • Transmitter Power Supply & Relays Coming Soon
  • 3 Year Warranty

Two relays, transmitter power, and serial communication options make the Trident a key player in any loop. The Trident’s relays can be programmed for just about any alarming or on-off control application. Users can select high or low trip-points, 0-100% deadband, time delay, fail-safe operation, pump alternation, and up to four reset modes. The Trident’s transmitter power supply delivers up to 200 mA. With the serial communication options and MeterView software the Trident can be programmed from a computer and act as a data logger.

OTHER FEATURES
  • User friendly menu structure --- Two menus: Main & Advanced
  • Main Menu --- Most common functions
  • Advanced Features Menu --- Less common functions
  • Setting Numeric Values --- Right arrow button selects next digit; Up arrow button increments digit value
  • Meter Copy --- Copy all settings to another meter in 5 seconds!
  • Standard feature --- no serial adapter needed

SPECIFICATIONS
Display 0.56•• (14.2 mm) red LEDs. Four digits (-1999 to 9999)
Front panel NEMA 4X, IP65. Panel gasket provided.
Programming methods Four front panel push buttons, PC and MeterView software, or cloning with Copy feature.
Noise filter Programmable between 2 and 199 (0 will disable filter).
Display update rate Process/RTD: 3.7-5/sec; T/C: 1.8-2.5/sec
Overrange Display flashes 9999
Underrange Display flashes -1999
Recalibration All inputs are calibrated at the factory.
Max/Min display Stored until reset by user or meter is turned off.
Non-volatile memory All programmed settings are stored in nonvolatile memory for a minimum of ten years if power is lost.
power AC: 85 - 265 VAC, 50/60 Hz, 20 VA; DC: 90-265 VDC, 20 W.
Option: 12-36 VDC or 12-24 VAC
Fuse Recommended external fuse: 1 A, 250 V slow blow
Normal Mode rejection 64 dB at 50/60 Hz
Isolation 4 kV
Environmental
  • Operating temperature range: 0 to +65°C
  • Storage temperature range: -40 to +85°C
  • Relative humidity: 0 to 90% non-condensing
Connection Power & Signal: removable screw terminal blocks accept 12 to 26 AWG. Serial: RJ11 header, standard on all meters.
Enclosure 1/8 DIN, high impact plastic, 94V-0, color; gray
Weight 8 oz (2.27 g) (no options)
Warranty 2 years parts and labor