- Measure and display high side, low side, and differential
pressure simultaneously from 0 to 300 psi (0 to 2068 kPa)
- Robust, splash-proof case
- Calculates flow using valve manufacturers’ Cv (Kv) factors
- Calculates heat flow, impeller diameter, and brake power
|
- Test and balance heating and cooling systems
- Check pump performance
HM670 kit includes hard carrying case, (2) 6.7 ft x ¼-in.
(2 m x 6 mm) hoses with shut-off valves, (2) B&G readout
probes, (2) P/T gauge adapter probes, and power cord.
HM680 kit includes all items in HM670 kit, plus a temperature
probe, CompuDat USB downloading software, and USB
interface cable. |
| Pressure |
| Differential Pressure |
0 to 300 psi (0 to 2068 kPa) |
| Gauge Pressure |
0 to 300 psi (0 to 2068 kPa) |
| Resolution (best) |
0.001 psi (0.01 kPa) |
| Accuracy1 |
±1% of reading or .072 psi (0.5 kPa),
whichever is greater |
| Units |
in. H2O, ft H2O, in. Hg, kPa, mm Hg, m H2O, psi, bar |
| Connection |
¼ in. (6.25 mm) 37° Flare Fitting, Male |
| Temperature |
| Operating (electronics) |
40 to 100°F (4 to 38°C) |
| Storage |
0 to 140°F (-18 to 60°C) |
| Media |
32 to 180°F (0 to 82°C) |
| Probe |
-40 to 250°F (-40 to 121 °C) |
| Resolution |
0.1°F (0.1°C)
|
| Accuracy |
±0.5°F (0.3°C) from 32 to 160°F (0 to 71°C);
max ± 2.0°F (1.2°C) from -40 to 32°F (-40 to 0°C)
and from 160 to 250°F (71 to 121°C) |
| Units |
°F, °C |
| Flow |
| Range2 |
0 to 2271 m3/h, 0 to 9,999 USGPM
(0 to 631 l/s) |
| Resolution (best) |
0.0001 USGPM (0.00001 l/s) |
| Accuracy |
per pressure accuracy + valve deviation |
| Units |
USGPM, UKGPM, m3/h, l/s, l/m |
| |
| Statistics |
min, max, average, sum up to 1000 readings (HM680 only) |
| Data Storage |
1000 combined readings, 100 Test IDs (HM680 only) |
| Logging Interval (HM680 only) |
User selectable, 5 to 3600 seconds |
| Averaging Interval (HM680 only) |
User selectable, 1 to 30 seconds |
| External Meter Dimensions |
11.1 in. × 4.7 in. × 3.5 in. (28.2 cm × 11.9 cm × 8.8 cm) |
| Meter Weight with Batteries |
2.65 lbs (1.20 kg) |
| Power Requirements |
Four AA-size cells, or AC adapter |
1 Accuracy statement applies from 0 to 250 psi (0 to 1724 kPa)
2 The flow reading is a calculated value determined from the measured Differential pressure,
user entered valve flow coefficient (Kv or Cv), and fluid specific gravity |