| Humidity and Temperature Transmitters for Industrial Applications |
| HMT330 Series |
| FEATURES AND BENEFITS |
|
|
|
The HUMICAP Humidity and Temperature Transmitter Series
HMT330 is designed for demanding industrial applications where stable measurement
and wide customization possibilities are important.
|
| HUMICAP PERFORMANCE |
| The HMT330 series incorporates Vaisala's 30 years of experience in industrial humidity measurement. The sensor measures accurately and reliably and is immune to particulate contamination and most chemicals. |
| CHEMICAL PURGE MINIMIZES EFFECTS OF CONTAMINANTS |
| Chemical purge minimizes effects of contaminants In environments with high concentrations of chemicals and cleaning agents, chemical purge helps to maintain the accuracy between calibration intervals. Chemical purge involves heating the sensor to remove harmful chemicals. The function can be initiated manually or programmed to occur at set intervals. |
| GRAPHICAL MEASUREMENT TREND AND HISTORY DISPLAY |
| The HMT330 can be ordered with a large numerical and
graphical display, allowing the user to easily monitor measurement trends
and I-year history. Data collection and transfer to PC |
| DATA COLLECTION AND TRANSFER TO PC |
| The recorded measurement data can be viewed on the display or transferred to PC with Windows based software. |
| MANY WAYS TO INSTALL |
| Mains and DC power options, and several mounting accessories make it easy to install the instrument. |
| VERSATILE OUTPUTS |
| The HMT330 can have up to three analog outputs. Galvanic isolation of supply power and analog outputs is also available. For digital communication, the RS-232, RS-485 or relay outputs can be used. |
| FLEXIBLE CALIBRATION |
|
|
| SPECIFICATIONS | |
| Performance | |
| Relative Humidity | |
| Measurement Range | 0 to 100% RH |
| Accuracy against factory standards including non-linearity, hysteresis and repeatability | |
|
at +20°C
|
± 1 %RH (0 to 90 %RH) ±1.7 %RH (90 to 100 %RH) |
|
at -20 to +40°C
|
± (1.0 + 0.008 x reading) %RH* |
|
at -40 to -20°C, +40 to +180°C
|
± (1.5 + 0.015 x reading) 90W |
| Factory calibration uncertainty** (+20°C) | 0 to 40 %RH: ± 0.6 %RH 40 to 97 %RH: ±1.0 %RH |
| Humidity sensors for typical applications | Vaisala HUMICAP 180 |
| Humidity sensors chemical purge/warmed probe | Vaisala HUMICAP 180C |
| Humidity sensors high chemical concentrations* | Vaisala HUMICAP 180L2* |
| * For Vaisala HUMICAP 180L2 sensor at -10...+40°C ± (1.0 + 0.01 x reading) %RH; at -40...-10°C,+40...+180°C ± (1.5 + 0.02 x reading) I/O RH | |
| ** Defined as +2 standard deviation limits. Response time (90 %) at 20°C in still air with grid filter: 8 s; with grid + steel netting filter: 20 s; with sintered filter: 40s | |
| Temperature | |
| Measurement range |
|
| Accuracy at +20°C | (+68°F) 0.2°C |
| Accuracy over temperature range | ![]() |
| Temperature sensor | Pt 100 RTD 1/3 Class B IEC 751 |
| Other variables available (depends on model) | dewpoint temperature, mixing ratio, absolute humidity, wet bulb temperature, enthalpy, water vapor pressure |
| Operating Environment | |
| Operating temp. for probe | Same as measurement ranges |
| Operating temp. for transmitter body | -40 to 60°C |
| Operating temp. for transmiter body with display | 0 to 60 °C |
| Operating pressure (HMT334) | 0 to 10 MPa (0 to 100 bar) |
| Operating pressure (HMT338) | 0 to 4 MPa (0 to 40 bar) |
| Operating pressure (HMT333, HMT335, HMT337) | Vapor tight |
| Electromagnetic compatibility | Complies with EMC standard EN61326-1:1997 + Am1:1998 + Am2:2001 |
| Inputs & Outputs | |
| Operating voltage | 10 to 35 VDC, 24 VAC |
| Operating voltage with optional power supply module | 100 to 240 VAC, 50/60Hz |
| Power consumption @ 20°C (Uin 24 VDC) | |
|
RS232
|
Max. 25mA |
|
Uout 2 x 0 to 1V / 0 to
5V / 0 to 10V
|
Max 25mA |
|
Iout 2 x 0 to 20mA
|
Max 60mA |
|
display and baclight
|
+20mA |
|
during probe heating (HMT337)
|
+120mA |
| Analog outputs (2 standard, 3rd optional) | |
|
current output
|
0 to 20mA, 4 to 20mA |
|
voltage output
|
0 to 1V, 0 to 5V, 0 to 10V |
| Accuracy of analog outputs @ 20°C | ±0.05% full scale |
| Temperature dependence of the analog outputs | ±0.005% full scale |
| External loads current outputs | RL < 500ohm |
| External loads 0 to 1V outputs | RL > 2 kohm |
| External loads 0 to 5V and 0 to 10V outputs | RL > 10 kohm |
| Max wire size | 0.5mm2 (AWG 20) stranded wires recommended |
| Digital outputs | RS232, RS485 (ptional) |
| Relay outputs (optional) | 0.5A, 250 VAC |
| Display | LCD with backlight, graphic trend display of any parameter |
| Menu languages | English, French, Spanish, German, Japanese, Swedish, Finnish |
| Mechanics | |
| Cable feed through alternatives cable bushing | M20 x 1.5 (cable diameter 8 to 11 mm) |
| Conduit fitting | M20 x 1.5 / 1/2 in. NPT |
| Conduit fitting 8-pole connector (male) | RSFM5 / 0.5 |
| Conduit fitting 8-pole connector with 5 m cable (female) | RKT5-24 / 3M |
| Probe cable diameter | HMT323: 6.0 mm; Other probes: 5.5 mm |
| Housing material | G-AlSi 10 Mg (DIN 1725) |
| Housing classification | IP 65 (NEMA 4) |