GENEQ > Météorologie > Enregistreurs – Miniatures

Enregistreur de données pour la température et l’humidité relative avec
transmission sans fil de Oakton


Ideal for monitoring temperature, humidity, and other parameters in supermarkets, storage, air conditioning and ventilation, clean rooms, warehouses, galeries and more!


FEATURES
  • Remote real-time monitoring of up to 200 dataloggers on one computer
  • Computer can receive data from loggers up to 120 meters away
  • Programmable audible and visual alarm for each datalogger
  • Each cradle is electronically labeled with an ID number or name
  • Easy-to-follow, color coded computed interface
  • License free wireless communication

LOGGERPLUS INTEGRATES
RH/TempLog or TempLog logger
Contains built-in sensors for temperature and humidity, plus a built-in external port for additional remote sensors
LoggerPlus Cradle
Transforms your logger into a wireless (RF) transmitter that sends readings at user-set intervals to the LoggerPlus receiver for observation and data storage
LoggerPlus Receiver
A small RF device that connects to your PC to receive wireless dtat from your loggers
MicroLab PlusSoftware
Allows custom, real-time monitoring of up to 200 loggers from a remotely located computer Daily down loading or continuous down loading mode is user selectable
Selectable Views
See each logger as a meter or an icon located on your photo or CAD drawing

FOR A COMPLETE SYSTEM
  • The quantity of loggers you require
  • One cradle for each logger
  • One receiver (per computer)
  • One MicroLab Plus Windows software package
  • Remote sensors as required - one/logger

SPECIFICATIONS
RH/Temp.Log and TempLog dataloggers
Temperature
Range -30 to 50°C (-22 to 122°F)
Resolution 0.5°C (1°F)
Accuacy ±0.6°C (1.1°F)
Humidity
Range 0 to 100% RH
Resolution 5%
Accuacy ±3% from 0 to 90% RH at room temp.;
±6% from 90% to 100% RH
General
Memory Stores up to 16 000 measurements
Output Infrared: IRDA (infrared Data Association) interface to printer or computer with IRDA port; RS232: Cable connection to your computer (order cable/software package separately)
Sampling Rate Selectable via software from once per 10 seconds to once per two hours
Software Required to download readings to a computer and to set sampling rate (order software separately). Software can be used with multiple loggers. Software is compatible with Windows 3.x and Windows 95/98/NT/ME CDRom
Display Two digit LCD display, 3/8 in. H, with mode indicators
Housing Temp.Log: IP65 rated; RH/TempLog: IP60 rated
Power Internal Lithium battery, 3.6V
Dimensions 2.8 in. diameter x 0.9 in. D (7.2 x 2.3 cm)
Weight 0.2lb (0.1kg)
Logger Cradle
  • Audible alarm, and LED alarm
  • serial communication
  • CE and FCC standard compliance
Channels RS232 at 19.2
Connectors 4-pin flat connector to logger, 4 pin flat connector to any external sensor, screw terminal for external DC supply
Power Supply
  • Internal: replaceable internal lithium battery, 3.6V 1/2AA
  • External: 6 to 30V minimum 300mA or use AC adapter
RF Transmission EMC conformant to ETS 300-683 Type approved to ETS 300-220; Useable range to 120m (35m indoors) 915.5 MHz, 1mW
LoggerPlus Receiver
Useable Range Up to 120m (35m indoors) One RS232 port to the computer (or USB)
Power Supply
  • Internal: Lithium battery, 3.6V, 2AH, AA
  • External AC/DC 6V adapter
RF Receiver
  • Red LED indicating RF signal
  • Green LED indicating valid dat being
  • Approved to ETS 300-220
  • CE and FCC standard compliance
MicroLab Plus Software
Data Display Capabilities
  • From up to 200 loggers
  • Real-Time temperature and humidity readings
  • Visual alarm when the logger crosses an upper or lower alarm threshold for temperature or humidity
  • Battery level
  • An Excel file containing all measured data received from the device
Set Up Capabilities
  • ID of each loggers
  • Alarm levels of each logger
  • Sampling rate from once every minute to every hour
  • Comments
  • Calibration and scaling external sensors
  • View as plant locations or on screen instruments
Min. Computer Requirements
  • Windows 95/98 and high
  • 6MB disk space
  • CD-ROM drive
  • Available communication port

CAT. NO. DESCRIPTION
WD-35710-00 Oakton TempLog Logs temperature
WD-35710-10 Oakton RH/TempLog Logs temperature and humidity
WD-35710-20 LoggerPlus transmitter & alarm cradle
WD-35710-25 LoggerPlus receiver, includes software, cable, and 110 VAC adapter
WD-35710-55 MicroLab Plus Windows software on CD-Rom
WD-35710-70 Temp. sensor, -50 to 100°C, stainless steel, 3.25L x 0.125 dia
WD-35710-72 Current sensor 0 to 20 mA
WD-35710-74 Voltage sensor 0 to 10V
WD-35710-76 Contact sensor
WD-35710-78 pH adapter with BNC connector 0 to 14 pH (pH electrode sold separately)
Accessories
WD-35710-63 AC/DC adapter, 110/VAC
WD-35710-64 AC/DC adapter, 220/VAC
WD-35710-65 Replacement 3.6V lithium battery
WD-35710-69 USB communication cable cradle to PC