GENEQ > Environment > Refrigeration
Digital Refrigerated Service Manifolds
Model Testokool

Fully Integrated Service Tools for ALL Refrigeration
Systems. Testokool digital refrigeration service manifolds provide complete
system information, pressures, temperatures and PT charts for all refrigerant
systems. Upgrade your gauges, instruments, thermometers, charts, and manifolds
with ONE easy-to-use-meter! Download logged data to a PC (560 only)
| IDEAL FOR |
|
| MEASURE AND RECORD |
|
| CALCULATE (35 built in refrigerants) |
|
| FEATURES |
|
| DATALOGGING AND STORAGE |
|
| DESIGNED FOR YEARS OF TROUBLE FREE USE |
|
| SPECIFICATIONS | |
| Dimensions | 7 x 4.5 x 1.5 |
| Housing protection | NEMA 12 (IP65) |
| Pressure/Vacuum accuracy | 0.5% full scale 1 digit |
| Ambient temp. compensation | from 14° to 122 °F |
| Battery | 9 volt |
| Battery life | 40 hrs. |
| System connection | 7/16 UNF |
| Separating membrane | 316L stainless steel |
| Operating/storage temp. | -4° to 140°F |
| Compatible with | any CFCs, CO2, fluorinated hydrocarbons, Nitrogen, Ammonia (551, 555-2, 556-2, 560-2 ONLY, Stainless Steel models) |
| Measuring units | Easily switch from English to Metric (SI) |
| Warranty | 2 years |
| PRODUCT SELECTION GUIDE | ||||
|
551
|
555
|
556
|
560
|
|
| Brass Order # |
0560 5551
|
0560 5561
|
0560 5601
|
|
| Stainless Steel Order # |
0560 5510
|
0560 5552
|
0560 5562
|
0560 5602
|
| Vacuum Range |
3 psi max. (200hPa)
|
-
|
-
|
3 psi max. (200hPa) above this auto ranges
to pressure sensor
|
| Vacuum Resolution |
0.1 micron
|
-
|
-
|
Down to 0.0001 psi (5 micron equiv.)
|
| Refrigerant Pressure Range |
-
|
725 psi (50bar) (abs)
|
725 psi (50bar) (abs)
|
725 psi (50bar) (abs)
|
| Pressure Resolution |
-
|
0.1 psi (0.1bar)
|
0.1 psi (0.1bar)
|
0.1 psi (0.1bar)
|
| Pressure Overload |
87 psi (6bar)
|
1087 psi (75bar)
|
1087 psi (75bar)
|
1087 psi (75bar)
|
| External Temp. Input(s) |
-
|
-
|
Up to 2 - Pt 100 (RDT or Platinum)
|
1 - Pt 100 (RDT or Platinum)
|
| Temp. Measurements Range |
-
|
-
|
-58 to 753°F
|
-58 to 753°F
|
| Memory Location |
3600*
|
3600*
|
3600*
|
32,000
|
| Data Interface |
N/A
|
N/A
|
External data button
|
RS232 to PC
|
| Pre-Loaded Refrigerants |
-
|
35
|
35
|
35
|
| Weight (approx.) |
1.25lbs
|
2lbs
|
2lbs
|
2.5lbs
|
| *Wrap around memory | ||||
| CAT. NO. | DESCRIPTION |
| Recommended Accessories | |
| 0609 5600 | External Temp Sensor (Velcro) (fits diameters from 1/4 to 4.5) |
| 0516 0008 | Rugged Carry Case |
| 0628 1085 | 120 Volt Power Supply (560 only) |
| 0554 5600 | PC Analysis Software (560 only) |
| 0628 0178 | RS232 Cable (560 only) |