GENEQ > Environment > Air Velocity Meters
| VelociCalc Multi-Function Thermal Anemometer |
| Model 9555 |
| Model 9555 |
| Features and Benefits |
| • Best in class accuracy, especially
in low flows • Displays up to 5 measurements simultaneously • Optional “smart” plug-in probes, including CO2 and rotating vane probes • Large graphic display • Manual or continuous data logging • TRAKPROTM downloading software included • Name test IDs meaningful to you • Bluetooth® printer capability • Fast calibration and repair service—just send in the probe |
| The Model 9555 series are portable,
hand held, Multi-Function Ventilation Test Instruments. These instruments
are available with or without a differential pressure sensor and are designed
to work with a wide range of plug-in probes. The probes allow users to
make various measurements by simply plugging in a different probe that
has the features and functions best suited for a particular application.
They are designed to measure air velocity, temperature, humidity, CO and
CO2. Calculations include air flow, heat flow, turbulence, wet bulb and
dew point temperature. The probes can be ordered at any time and include
a data sheet with certificate of traceability. When its time for servicing,
only the probe needs to be returned since all the calibration data is
stored within the probe. Applications • HVAC commissioning and troubleshooting • Clean room certification • Testing and balancing • Ventilation evaluations • Thermal comfort studies • IAQ investigations • Process air flow testing |
| Specifications VELOCICALC Models 9555, 9555-A, 9555-P, and 9555-X |
|
| Velocity (TA Probe) | |
| Range | 0 to 9,999 ft/min (0 to 50 m/s) |
| Accuracy1&2 | ±3% of reading or ±3 ft/min (±0.015 m/s), whichever is greater |
| Resolution | 1 ft/min (0.01 m/s) |
| Velocity (Pitot Tube for Meter Models 9555, 9555-A, 9555-P) | |
| Range3 | 250 to 15,500 ft/min (1.27 to 78.7 m/s) |
| Accuracy4 | 2,000 ft/min (±1.5% at 10.16 m/s) |
| Resolution | 1 ft/min (0.01 m/s) |
| Velocity (Rotating Vane Probe Model 995) | |
| Range | 50 to 6,000 ft/min (0.25 to 30 m/s) |
| Accuracy | ±1% of reading or ±4 ft/min (±0.02 m/s) |
| Resolution | 1 ft/min (0.01 m/s) |
| Duct Size | |
| Dimensions | 1 to 250 inches in increments of 0.1 in. (1 to 635 cm in increments of 0.1 cm) |
| Volumetric Flow Rate | |
| Range | Actual range is a function of velocity, pressure, duct size, and K factor) |
| Temperature (TA Probe Models 964, 966, 980, 983) | |
| Range | 14 to 140°F (-10 to 60°C |
| Accuracy5 | ±0.5°F (±0.3°C) |
| Resolution | 0.1°F (0.1°C) |
| Temperature (TA Probe Models 960, 962) | |
| Range | 0 to 200°F (-18 to 93°C) |
| Accuracy5 | ±0.5°F (±0.3°C) |
| Resolution | 0.1°F (0.1°C) |
| Temperature (Rotating Vane Probe Model 995) | |
| Range | 32 to 140°F (-0 to 60°C) |
| Accuracy5 | ±2.0°F (±0.1°C) |
| Resolution | 1.0°F (0.1°C) |
| Relative Humidity (TA Probe Models 964, 966, 980, 982) | |
| Range | 32 to 140°F (-0 to 60°C) |
| Accuracy6 | ±2.0°F (±0.1°C |
| Resolution | 1.0°F (0.1°C) |
| Relative Humidity (TA Probe Models 964, 966, 980, 982) | |
| Range | 0 to 95% RH |
| Accuracy6 | ±3% RH |
| Resolution | 0.1% RH |
| Carbon Monoxide (IAQ Probe with CO Model 982) | |
| Range | 0 to 5000 ppm |
| Accuracy6 | ±3% of reading or ±50 ppm, whichever is greater |
| Resolution | 1 ppm |
| Static/Differential Pressure (Probe for Meter Models 9555, 9555-A, 9555-P) | |
| Range7 | -15 to +15 in. H2O (-28.0 to +28.0 mm Hg, -3735 to +3735 Pa) |
| Accuracy | ±0.01 mm Hg, ±0.005 in. H2O (±1% of reading ±1 Pa) |
| Resolution | 0.001 in. H2O (1 Pa, 0.01 mm Hg) |
| Barometric Pressure | |
| Range | 2.036 to 36.648 in. Hg (517.15 to 930.87 mm Hg) |
| Accuracy | 2% of reading |
| Instrument Temperature Range | |
| Operating (Electronics) | 40 to 113°F (5 to 45°C) |
| Storage | -4 to 140°F (-20 to 60°C) |
| Data Storage Capabilities | |
| Range | 26,500+ samples and 100 test IDs |
| Logging Interval | |
| 1 second to 1 hour | |
| Time Constant | |
| User selectable | |
| External Meter Dimensions | |
| 3.8 in. x 8.3 in. x 2.1 in. (9.7 cm x 21.1 cm x 5.3 cm) | |
| Meter Weight with Batteries | |
| 0.8 lbs. (0.36 kg) | |
| Meter Probe Dimensions | |
| Probe Length | 40 in. (101.6 cm) |
| Probe Diameter of Tip | 0.28 in. (7.0 mm) |
| Probe Diameter of Base | 0.51 in. (13.0 mm) |
| Articulating Probe Dimensions | |
| Articulating Section Length | 6.4 in. (16.26 cm) |
| Diameter of Articulating Knuckle | 0.38 in. (9.5 mm) |
| Power Requirements | Four AA-size batteries or AC adapter |
| Optional Probes for VELOCICALC 9555 Series Multi-Functional Anemometers | |
|
Model |
Probe Description |
|
960 |
Air Velocity and Temperature, straight probe |
|
962 |
Air Velocity and Temperature, articulating probe |
|
964 |
Air Velocity, Temperature, and Humidity, straight probe |
|
966 |
Air Velocity, Temperature, and Humidity, articulating probe |
|
995 |
100 mm Rotating Vane probe |
|
968 |
Draft and Comfort probe |
|
972 |
Surface Temperature probe |
|
974 |
Air Temperature probe |
|
980 |
Indoor Air Quality probe |
|
982 |
Indoor Air Quality probe, with CO |
| 9555 |
9555-A |
9555-P |
9555-X |
|
| Probe that measures velocity, temperature, and humidity | straight |
articulated |
optional |
optional |
| Pressure measurement | • |
• |
• |
|
| Calculates flow, wet bulb, dew point, standard/actual | • |
• |
optional |
optional |
| Optional velocity and temperature probe | • |
• |
• |
• |
| Optional rotating vane probe | • |
• |
• |
• |
| Optional IAQ probes (CO2, temperature, humidity, CO) |
• |
• |
• |
• |
| Data Logging (manual, auto save continuous) | • |
• |
• |
• |
| Data logging software | • |
• |
• |
• |
| Free Certificate of Calibration | • |
• |
• |
• |
| • 1 Temperature compensated over an air
temperature range of 5 to 65°C (40 to 150°F). • 2 The accuracy statement begins at 0.15 m/s through 50 m/s (30 ft/min through 9,999 ft/min). • 3 Pressure velocity measurements are not recommended below 5 m/s (1000 ft/min) and are best suited to velocities over 2,000 ft/min (10.00 m/s). Range can vary depending on barometric pressure. • 4 Accuracy is a function of converting pressure to velocity. Conversion accuracy improves when actual pressure values increase. • 5 Accuracy with instrument case at 25°C (77°F), add uncertainty of 0.03°C/°C (0.05°F/°F) for change in instrument temperature. • 6 Accuracy with probe at 25°C (77°F). Add uncertainty of 0.2% RH/°C (0.1% RH/°F) for change in probe temperature. Includes 1% hysteresis. • 7 Overpressure range = 190 in. H2O, 360 mmHg, 48 kPa. |
||||